16 сент. 2015 г. · If you want conduit, use 2" with four conductors (2/0-2/0-2/0-4 Al THHN) or 1 1/2" conduit with four conductors (1-1-1-6 Cu THHN). |
24 сент. 2019 г. · At 125 amps you'd normally use 1 gauge THHN which can carry 130 amps but based on distance you're going to go up a size to minimize voltage loss ... |
15 мар. 2021 г. · You could use a 1/0 SER cable. It is rated for 120 amps, but since they do not make a 120 amp breaker, you are allowed to size up to the next available size. |
23 мая 2023 г. · youll need at least 2/0 AL for 125a before voltage drop calcs.... there is a tutorial on wire sizing on the electrical FAQ sticky |
26 апр. 2020 г. · If I should be sizing to 125A, then it would be 1AWG Copper (1-1-1-3 SER) or 1/0 Aluminum (1/0-1/0-1/0-2 SER). |
29 мар. 2018 г. · Since there are no 135A breakers you are allowed to use the next closest larger size, which is 150A, but your load must be below 135 amps. |
25 сент. 2016 г. · Are the three wires (2 AWG Copper) the right size for the 125' run (as I think it is the largest wire that a QO 90Amp breaker will accept)? |
23 июн. 2019 г. · 2 gauge aluminum will be good to 90A. 1/0 is right for 125A you'll need two ground rods, and it will have to be a 4-wire feeder as well. |
7 мар. 2011 г. · Bare minimum is 1 1/4" but if 2" is used it will be easier to pull then a smaller size w/ a limited increase in cost. As for wire size, #3 AWG copper or #1 AWG ... |
19 февр. 2014 г. · You only can if the panel says you can. The maximum branch circuit breaker rating will be on the label inside the panel. |